5.9 Error status
Some of the Sakura responses includes an error status. The error status values are
specified in Table 5-7.
It is possible to configure the tank hub error status and to change the error status value
range from 30h-33h to 40h-43h. The error status configuration is described in Table 5-6.
Table 5-7: Error Status
Value Decoded
ASCII char
Description
30h 0 No error
31h 1 Over Tension
32h 2 Under Tension
33h 3 Sensor error
5.10 Alarms
An alarm status is included in some of the Sakura V1 protocol responses. There are two
alarms available: Alarm 1 and Alarm 2. The alarm status value is customized as described in
Table 5-8.
Table 5-8: Alarm Status
Value Decoded
ASCII char
Description
30h 0 No alarm
31h 1 Alarm 1
32h 2 Alarm 2
33h 3 Alarm 1 and Alarm 2
The following inputs can be mapped to the alarms:
• High and/or low alarm level limits
• Digital input relays K1 and K2
The desired alarm options are enabled in holding register Sakura_Alarm_Conf (1213), and
the alarm level limits are configured in the generic TMV Alarm holding registers (one set of
parameters for each tank position).
5.10.1 Configure Sakura V1 alarms
To configure the Sakura V1 alarms, do the following:
Manual Supplement Optional configuration and settings
00809-0800-2410 August2023
Emerson.com/Rosemount 27