Procedure
1. Specify the desired alarm level limits (High and Low) in the generic TMV Alarm
holding registers for desired tank positions, holding register block 2400-2478.
Example: Holding register 2400 and 2402 are used to set alarm level limits for tank
position 1.
2. Enable desired Alarm 1 and/or Alarm 2 options in holding register 1213.
a) Double-click the grey colored Value field.
Optional configuration and settings Manual Supplement
August2023 00809-0800-2410
28 Emerson.com/Rosemount