Figure 5-1: Example: Holding Register Sakura_BaudRate (1217) Set to Value 0
Note
The baud rate value is only updated after restart or if the Sakura bus is idle for at least 60
seconds.
5.6
Invalid level measurements
The tank hub reply on the Sakura host level request can be customized if the level value is
invalid.
Use holding register Sakura_LevelErrorConfig (1211) to customize your reply configuration,
see Table 5-2. This configuration is applicable on all tank positions.
Table 5-2: Holding Register Sakura_LevelErrorConfig 1211
Value Value definition Description
0 Default The tank hub will reply with the default level value 99999.9
mm. It is recommended to keep the configuration as Default.
1 Last Valid The tank hub will reply with the last good level value.
2 Invalid Value The tank hub will reply with the level value that is present in
the tank hub even if the level is considered to be invalid.
3 User Defined The tank hub will reply will level value configured in holding
registers 1204 and 1205 (see Table 5-3).
Figure 5-2 shows an example where holding register Sakura_TempErrorConfig (1211) is set
to value 0. The tank hub will reply with the default level value 99999.9 mm.
Optional configuration and settings Manual Supplement
August2023 00809-0800-2410
22 Emerson.com/Rosemount