10. Using Up or Down, select 1 Yes or 2 No. Press ENTER.
If No, the process repeats from Step 6.
The Field Communicator displays Setting Fld dev output to 20 mA.
11. Press OK.
The Field Communicator displays Fld output 20.00 mA equal to reference
meter?
12. Using Up or Down, select 1 Yes or 2 No. Press ENTER.
If No, the process repeats from Step 9.
The Field Communicator displays NOTE: Loop may be returned to
automatic control.
Manual Using HART
®
communications