Unidrive SP Regen Installation Guide 125
Issue Number: 2 www.controltechniques.com
The following modes are available for the analogue input 2. A current loop loss trip is generated if the input current falls below 3mA. In modes 4 and
5 the analogue input level goes to 0.0% if the input current falls below 3mA.
The following modes are available for the analogue input 3. A current loop loss trip is generated if the input current falls below 3mA. In modes 4 and
5 the analogue input level goes to 0.0% if the input current falls below 3mA.
7.11 T7 analogue input 2 mode
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 111
Range Regen 0 to 6
Default Regen 6
Update rate Background read
Parameter value Parameter string Mode Comments
0 0-20 0 - 20mA
1 20-0 20 - 0mA
2 4-20.tr 4 -20mA with trip on loss Trip if I < 3mA
3 20-4.tr 20 - 4mA with trip on loss Trip if I < 3mA
4 4-20 4 - 20mA with no trip on loss
5 20-4 20 - 4mA with no trip on loss 0.0% if I < 4mA
6 VOLt Voltage mode
7.12 T7 analogue input 2 scaling
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
3111
Range Regen 0.000 to 4.000
Default Regen 1.000
Update rate Background
7.13 T7 analogue input 2 invert
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
111
Default Regen 0
Update rate Background
7.14 T7 analogue input 2 destination
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1 2 1111
Range Regen Pr 0.00 to Pr 21.51
Default Regen Pr 3.10
Update rate Background
7.15 T8 analogue input 3 mode
Drive mode Regen
Coding
Bit SP FI DE Txt VM DP ND RA NC NV PT US RW BU PS
1111
Range Regen 0 to 9
Default Regen 6
Update rate Background