3 – 9
Section 3 • Installation
VSS/VSM/VSH/VSSH • Installation, Operation and Maintenance Manual • Emerson • 35391SD
Figure 3-7. Level Compressor Unit Using Top Surface of Spherical Washers
SPHERICAL
WASHERS
LEVEL
Figure 3-6. Housekeeping Pad Dimension Detail - Top View
5/8" DIA. HILTI HAS SS THREADED ROD
(HAS-E RODS ARE ACCEPTABLE FOR INTERIOR
INSTALLATIONS) INSTALLED USING
HIT-ICE/HIT-HY 150 ADHESIVE ANCHORING
SYSTEM.
(5" PROJECTION, 12 3/8" EMBEDMENT.)
HOLES TO BE INSTALLED WITH HAMMER DRILL.
DO NOT DIAMOND CORE.
( T Y P. )
CENTER LINE
G.A.
G.A.
G.A.
G.A.
G.A. + 2"
G.A.G.A.
1" (TYP.)
(5) - # 6 VERT.
WITH STD. 90° HOOK
AT BOTTOM EACH
FACE
(2) - # 4
CLOSED TIES
COMPRESSOR UNIT
HOUSEKEEPING PADS