4.5.2 How to disabled/enabled an output during a maintenance section.
To disabled an output during a maintenance session means to exclude the output from the
regulation:
To do it act as in the following
1. Enter the COMPRESSOR SERVICE sub-menu, as described in the previous paragraph.
2. Select the load by means of the UP and DOWN keys.
3. Push the SET key, then use the UP and DOWN keys to move the status to ON to OFF
and vice versa.
4. Confirm the selection by means of the SET key.
4.5.3 Regulation with some outputs disabled.
If some outputs are disabled they don’t take part to the regulation, so the regulation goes on with the
other outputs.
4.5.4 How to display the running hours of a load.
The controller memorises the running hours of each load.
To see how long a load has been working enter the COMPRESSOR SERVICE sub-menu.
The running hour are displayed with the following layout: