1592021021 XC1008-1011-1015D GB A5 r.1.5A 12.10.2009 XC1008-1011-1015D 30/66
noCRO = it disables the set point coming from the supervising system, and it restores SETC1 and
SETC2 set.
noSTD1 = it disables the dynamic set point on the circuit 1, and it restores SETC1 and SETF1 set.
noSTD2 = it disables the dynamic set point on the circuit 2, and it restores SETC2 and SETF2 set.
DI16 Delay of configurable d.i. 1 (0 ÷ 255 min)
DI17 Polarity of configurable digital input 2 (term 38-39)
oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
DI18 Function of configur. configurable digital input 2 (term. 38-39)
ES1 = energy saving circuit 1
ES2 = energy saving circuit 2
OFF1 = circuit 1 stand –by
OFF2 = circuit 2 stand –by
LL1 = liquid level alarm for circuit 1
LL2 = liquid level alarm for circuit 2
noCRO = it disables the set point coming from the supervising system, and it restores SETC1 and
SETC2 set.
noSTD1 = it disables the dynamic set point on the circuit 1, and it restores SETC1 and SETF1 set.
noSTD2 = it disables the dynamic set point on the circuit 2, and it restores SETC2 and SETF2 set.
DI19 Delay of configurable d.i. 2 (0 ÷ 255 min)
DI20 Polarity of configurable digital input 3 (term 40-41)
oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
DI21 Function of configur. configurable digital input 3 (term. 40-41)
ES1 = energy saving circuit 1
ES2 = energy saving circuit 2
OFF1 = circuit 1 stand –by
OFF2 = circuit 2 stand –by
LL1 = liquid level alarm for circuit 1
LL2 = liquid level alarm for circuit 2
noCRO = it disables the set point coming from the supervising system, and it restores SETC1 and
SETC2 set.
noSTD1 = it disables the dynamic set point on the circuit 1, and it restores SETC1 and SETF1 set.
noSTD2 = it disables the dynamic set point on the circuit 2, and it restores SETC2 and SETF2 set.
DI22 Delay of configurable d.i. 3 (0 ÷ 255 min)
DI23 Polarity of configurable digital input 4 (term. 42-43)
oP: the digital input is activated by opening the contact;
CL: the digital input is activated by closing the contact.
DI24 Function of configur. configurable digital input 4 (term. 42-43)
ES1 = energy saving circuit 1
ES2 = energy saving circuit 2
OFF1 = circuit 1 stand –by
OFF2 = circuit 2 stand –by
LL1 = liquid level alarm for circuit 1
LL2 = liquid level alarm for circuit 2
noCRO = it disables the set point coming from the supervising system, and it restores SETC1 and
SETC2 set.
noSTD1 = it disables the dynamic set point on the circuit 1, and it restores SETC1 and SETF1 set.
noSTD2 = it disables the dynamic set point on the circuit 2, and it restores SETC2 and SETF2 set.
DI25 Delay of configurable d.i. 4 (0 ÷ 255 min)
DI26 Relay activated in case of liquid level alarm – circuit 1
nu = no relay activation, only visual signalling; Alr: all the C(i) outputs set as ALr; ALr1: all the C(i)
outputs set as ALr1, ALr2: all the C(i) outputs set as ALr2
DI27 Relay activated in case of liquid level alarm – circuit 2
nu = no relay activation, only visual signalling; Alr: all the C(i) outputs set as ALr; ALr1: all the C(i)
outputs set as ALr1, ALr2: all the C(i) outputs set as ALr2