iTEMP TMT112 Commissioning
Endress+Hauser 19
10 to 75 mV –10 mV 75 mV
10 to 400 Ω 10 Ω 400 Ω
10 to 2 000 Ω 10 Ω 2 000 Ω
Pt100 DIN –200 °C (–328 °F) 850 °C (1 562 °F)
Pt100 JIS –200 °C (–328 °F) 649 °C (482 °F)
Pt500 –200 °C (–328 °F) 250 °C (482 °F)
Pt1000 –200 °C (–328 °F) 250 °C (482 °F)
Ni100 –60 °C (–76 °F) 180 °C (356 °F)
Ni500 –60 °C (–76 °F) 150 °C (302 °F)
Ni1000 –60 °C (–76 °F) 150 °C (302 °F)
Polynom RTD –270 °C (–454 °F) 2 500 °C (4 532 °F)
Type B 0 °C (32 °F) 1 820 °C (3 308 °F)
Type C 0 °C (32 °F) 2 320 °C (4 208 °F)
Type D 0 °C (32 °F) 2 495 °C (4 523 °F)
Type E –270 °C (–454 °F) 1 000 °C (1 832 °F)
Type J –210 °C (–346 °F) 1 200 °C (2 192 °F)
Type K –270 °C (–454 °F) 1 372 °C (2 501 °F)
Type L –200 °C (–328 °F) 900 °C (1 652 °F)
Type N –270 °C (–454 °F) 1 300 °C (2 372 °F)
Type R –50 °C (–58 °F) 1 768 °C (3 214 °F)
Type S –50 °C (–58 °F) 1 768 °C (3 214 °F)
Type T –270 °C (–454 °F) 400 °C (752 °F)
Type U –200 °C (–328 °F) 600 °C (1 112 °F)
Polynom TC –270 °C (–454 °F) 2 500 °C (4 532 °F)
Pt100 DIN
Temp. Compensation Selection of temperature compensation of the cold junction when using customer specific
linearization of the TC polynom
Input: None, Type B, Type C, Type D, Type E, Type J, Type K, Type L, Type N, Type R, Type S,
Type T, Type U
None
Unit
Measuring unit
Enter engineering units.
Entry:
°C
°F
K
°C