Commissioning iTEMP TMT112
16 Endress+Hauser
Source for device description files
The suitable device driver software (DD/DTM) for the individual operating tools can be
acquired from a variety of sources:
www.endress.com --> Downloads --> Search field: Software --> Software type: Device driver
www.endress.com --> Products: individual product page, e.g. TMTxy --> Documents/
Manuals/Software: Electronic Data Description (EDD) or Device Type Manager (DTM).
Via DVD (please contact your local Endress+Hauser Sales Center)
Endress+Hauser supports all common operating tools from a variety of manufacturers (e.g.
Emerson Process Management, ABB, Siemens, Yokogawa, Honeywell and many others).
Endress+Hauser's FieldCare and DeviceCare operating tools are available for download
(www. endress.com --> Downloads --> Search field: Software --> Application software) or on
the optical data storage medium (DVD) which you can obtain from your local Endress +Hauser
Sales Center.
7 Commissioning
7.1 Installation and function check
Installation check
Before commissioning the measuring point make sure that all final checks have been carried
out:
"Post-installation check" checklist →  12
"Post-connection check" checklist →  15
Function check
Measuring the analog 4 to 20 mA output signal or following failure signals:
Measurement range undercut linear fall to 3.8 mA
Measurement range excess linear rise to 20.5 mA
Measurement range undercut
Sensor break; sensor short circuit
1)
≤ 3.6 mA or ≥21 mA
1) not for thermocouples
7.2 Commissioning
Once the power supply has been connected, the DIN rail temperature transmitter is
operational.
7.2.1 Quick setup
Using the Quick Setup, the operator is led through all the most important unit functions that
must be set up for standard measurement operation of the unit. Using the ’HART®
Communicator’ a quick setup of the black highlighted fields of the HART® function matrix is
possible.