Technical data TMT84
46 Endress+Hauser
Input signal Input data: The head transmitter is able to receive a cyclic value and its status sent by a master via
PROFIBUS
®
PA. That value and status is represented and can be read acyclically.
10.0.2 Output
Output signal • PROFIBUS
®
PA in accordance with EN 50170 Volume 2,
IEC 61158-2 (MBP), galvanically isolated;
Amendment 2 “Condensed status and diagnostic messages”
Amendment 3 “Identification and Maintenance Functions”
• FDE (Fault Disconnection Electronic) = 0 mA
• Data transmission rate: supported baud rate = 31.25 kBit/s
• Signal coding = Manchester II
• Output data:
Available values via AI blocks: temperature (PV), temp sensor 1 + 2, terminal temperature
• In a control system the head transmitter always operates as a slave and, dependent on the
application, can exchange data with one or more masters.
• In accordance with IEC 60079-27, FISCO/FNICO
Breakdown information Status message in accordance with PROFIBUS
®
PA Profile 3.01/3.02 specification.
Linearization/transmission
behavior
Temperature linear, resistance linear, voltage linear
Mains voltage filter 50/60 Hz
Galvanic isolation U = 2 kV AC (sensor input to the output)
Current consumption 11 mA
Switch-on delay 8 s
Thermocouples (TC)
As per IEC 584, part 1
As per ASTM E988
As per DIN 43710
Type B (PtRh30-PtRh6)
Type E (NiCr-CuNi)
Type J (Fe-CuNi)
Type K (NiCr-Ni)
Type N (NiCrSi-NiSi)
Type R (PtRh13-Pt)
Type S (PtRh10-Pt)
Type T (Cu-CuNi)
Type C (W5Re-W26Re)
Type D (W3Re-W25Re)
Type L (Fe-CuNi)
Type U (Cu-CuNi)
0 to +1820 °C (32 to 3308 °F)
-270 to +1000 °C (-454 to 1832 °F)
-210 to +1200 °C (-346 to 2192 °F)
-270 to +1372 °C (-454 to 2501 °F)
-270 to +1300 °C (-454 to 2372 °F)
-50 to +1768 °C (-58 to 3214 °F)
-50 to +1768 °C (-58 to 3214 °F)
-270 to +400 °C (-454 to 752 °F)
0 to +2315 °C (32 to 4199 °F)
0 to +2315 °C (32 to 4199 °F)
-200 to +900 °C (-328 to 1652 °F)
-200 to +600 °C (-328 to 1112 °F)
• 2-wire connection
• Internal reference junction (Pt100, class A)
• External reference junction: value adjustable -40 to +85 °C (-40 to +185 °F)
• Maximum sensor resistance 10k (if sensor resistance is greater than 10k, an
error message as per NAMUR NE89 is output)
Voltage transmitter (mV) Millivolt transducer (mV) -20 to 100 mV
-5 to 30 mV
Type of input Designation Measuring range limits