11 Operation using PROFIBUS
®
PA TMT84
70 Endress + Hauser
Input Range and
Mode n
read/
write
Configuration of the input measurement range.
0: mV, range 1: -5 to 30 mV; range: -5 to 30 mV; min.
span: 1 mV
1: mV, range 2: -20 to 100 mV; min. span: 1 mV
128: Ohm, range 1: 10 to 400 Ohm;
min. span: 10 Ohm
129: Ohm, range 2: 10 to 2000 Ohm;
min. span: 10 Ohm
Factory settings:
128: Ohm, range 1: 10 to 400 Ohm; min. span: 10 Ohm
Unit n read/
write
Configuration of the temperature unit for PV value n
Options:
1000 - K
1001 - °C
1002 - °F
1003 - Rk
1281 - Ohm
1243 - mV
1342 - %
Factory settings:
° C
Connection type n read/
write
Sensor connection mode:
Sensor Transducer 1 (Connection mode 1):
•0 - 2 wires
•1 - 3 wires
•2 - 4 wires
Factory settings:
3 wires
Sensor Transducer 2 (Connection mode 2):
•0 - 2 wires
•1 - 3 wires
Factory settings:
3 wires
Sensor 1 / Sensor 2
Menu item Parameter
"Sensor"
Submenu
"Sensor 1" or "Sen-
sor 2"
Name
Parame-
ter access
Description