Diagnosis bits TMT84, 3.02 (1)
Diagnosis Extension Bit
Diag Bit 56 not sup. by GSD
901: Ambient temperature undershoot
902: Ambient temperature overshoot
Diag Bit 59-71 not sup. by GSD
261: Electronic failure
431: No calibration TRD1
431: No calibration TRD2
283: Memory error
437: Configuration error TRD1
437: Configuration error TRD2
502: Linearization error TRD1
502: Linearization error TRD2
221: Reference measurement
041: Sensor 1 break
041: Sensor 2 break
043: Sensor 1 shortcut
043: Sensor 2 shortcut
042: Sensor 1 corrosion
042: Sensor 2 corrosion
103: Sensor drift detected TRD1
103: Sensor drift detected TRD2
104: Backup active TRD1
104: Backup active TRD2
101: Sensor 1 range undershoot
101: Sensor 2 range undershoot
102: Sensor 1 range overshoot
102: Sensor 2 range overshoot
482: Simulation active AI1
482: Simulation active AI2
482: Simulation active AI3
482: Simulation active AI4
501: Device Preset
262: Display communication failure
Diag Bit 101-103-71 not sup. by GSD
EXT_DIAG in Station_Status_1
SV1 Status
SV2 Status
RJ1 Status
RJ2 Status
PV1 Status + PV2 Status
Pos. 56 57 58 59-71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98 99 100 101-103
No. 1.0 1.1 1.2 1.3-2.7 3.0 3.1 3.2 3.3 3.4 3.5 3.6 3.7 4.0 4.1 4.2 4.3 4.4 4.5 4.6 4.7 5.0 5.1 5.2 5.3 5.4 5.5 5.6 5.7 6.0 6.1 6.2 6.3 6.4 6.5-6.7 1.3
Electr. module 1 F 261 0 D 1 1
0x24 0x24 0x24 0x24 0x24
Calibration 2 F 431 1 D 1 1
0x24 - 0x24 - )
1
Calibration 2 F 431 2 D 1 1
- 0x24 - 0x24 )
1
Memory contents 3 F 283 0 D 1 1
0x24 0x24 0x24 0x24 0x24
Configuration 4 F 437 1 S/P 1 1
0x24 - 0x80 0x80 )
1
Configuration 4 F 437 2 S/P 1 1
- 0x24 0x80 0x80 )
1
Linearization 5 F 502 1 S 1 1
0x24 - 0x80 0x80 )
1
Linearization 5 F 502 2 S 1 1
- 0x24 0x80 0x80 )
1
Ref. measurement 6 F 221 0 D 1 1
0x24 0x24 0x24 0x24 0x24
Break 7 F 41 1 S 1 1
0x24 - 0x80 0x80 )
1
Break 7 F 41 2 S 1 1
- 0x24 0x80 0x80 )
1
Shortcut 8 F 43 1 S 1 1
0x24 - 0x80 0x80 )
1
Shortcut 8 F 43 2 S 1 1
- 0x24 0x80 0x80 )
1
Corrosion 9 M/F 42 1 S 1 0/1
0xA4 /
(0x24) - 0x80 0x80 )
1
Corrosion 9 M/F 42 2 S 1 0/1
-
0xA4 /
(0x24) 0x80 0x80 )
1
Drift 10 M/F 103 1 P 1 0/1
- - 0x80 0x80
0xA4 /
0x24
Drift 10 M/F 103 2 P 1 0/1
- - 0x80 0x80
0xA4 /
0x24
Backup active 11 M 104 1 P 10
0x80 0x80 0x80 0xA4
Backup active 11 M 104 2 P 10
0x80 0x80 0x80 0xA4
Underrange 12 S/F 101 1 S 1 0/1
0x78 /
0x24 - 0x80 0x80 )
1
Underrange 12 S/F 101 2 S 1 0/1
-
0x78 /
0x24 0x80 0x80 )
1
Overrange 13 S/F 102 1 S 1 0/1
0x78 /
0x24 - 0x80 0x80 )
1
Overrange 13 S/F 102 2 S 1 0/1
-
0x78 /
0x24 0x80 0x80 )
1
Ambient temp. 14 S F 901 0 D 1 0/1
0x78 /
0x24
0x78 /
0x24
0x78 /
0x24
0x78 /
0x24
0x78 /
0x24
Ambient temp. 15 S F 902 0 D 1 0/1
0x78 /
0x24
0x78 /
0x24
0x78 /
0x24
0x78 /
0x24
0x78 /
0x24
Simulation active 16 C 482 1 P 10
Simulation active 16 C 482 2 P 10
Simulation active 16 C 482 3 P 10
Simulation active 16 C 482 4 P 10
Device Preset 17 C 501 0 D 10
Initialization 18 C 402 0 D 0
0x3C 0x3C 0x3C 0x3C 0x3C
Module connect. 19 M 262 0 D 10
)
1
For the status of the single sensor channel observe the appendix 'PV status handling'
doesn't remain at 0x80 but changes to 0xA4, because category is set to M
doesn't remain at 0x80 but changes to 0xA4, because category is set to M
Diagnosis Short Text
Classification
ID
Profile 3.01 with Amendment 2
Category (default)
Diagnosis code
Category (set by parameterization)
Channel