EasyManua.ls Logo

Endress+Hauser Levelflex FMP54 - Page 38

Endress+Hauser Levelflex FMP54
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Levelflex FMP51, FMP52, FMP54
38 Endress+Hauser
-80 (-3.15)
-100 (-3.94)
-120 (-4.72)
-60 (-2.36)
-40 (-1.57)
-20 (-0.79)
0
20 (0.79)
40 (1.57)
60 (2.36)
80 (3.15)
100 (3.94)
120 (4.72)
DC = 2
DC = 80
30 (0.79)
A
D
0
50 (1.97)
100 (3.94)
150 (5.91)
200 (7.87)
250 (9.84)
300 (11.8)
A0021483
 15 Measuring error at the end-of-probe for probes with metallic centering disk (product structure: feature
610 "Accessory mounted", option OA, OB or OC)
A Distance from probe end [mm(in)]
D Measuring error: Sum of non-linearity, non-repeatability and hysteresis
If for rope probes the DC value is less than 7, then measurement is not possible in the area of
the straining weight (0 to 250 mm from end of probe; lower blocking distance).

Table of Contents

Other manuals for Endress+Hauser Levelflex FMP54

Related product manuals