Levelflex M FMP41C with HART/4...20 mA Installation
Endress + Hauser 17
Type of probe mounting
When installing in plastic tanks, the nozzle must have at least DN50/2". The appropriate flange
must be used as the process connection.
For nozzles up to 450 mm high, select the length of the centering rod appropriate for the nozzle
height when using rope probes.
Use spring washers (1) (see Figure below).
Note!
It is recommended to retighten the flange bolts periodically, depending on process temperature
and pressure. Recommended torque: 60...100 Nm.
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment.
L00-FMP41Cxx-17-00-00-en-005
The coupling nut must be tightened using a torque of 5 up to a maximum of 10 Nm when installing
the FMP41C in the universal adapter ("Welding boss for adapter 43 mm" ä 61).
Supporting probes against warping
For WHG or Ex approval:
For probe lengths 3 m a support is required (see figure).
L00-FMP4xxxx-17-00-00-en-065
1
£ 450 mm / 18
spring washers
Ø <25 mm
>50 mm
Probe rod c
(FMP 41 C)
oated
Short metal pipe
e.g. welded in place
Plastic sleeve
e.g. PTFE, PEEK or PPS
e.g. 3 mm