Levelflex M FMP41C with HART/4...20 mA Commissioning
Endress + Hauser 57
Basic Setup step 6/6:
• This step starts the tank mapping
• The measured distance and the current measured value are always displayed in the header
• for a description, → ä 48)
l00-fmp4xxxx-20-00-00-en-004
6.8.1 Blocking distance
!
Note!
Please reenter the blocking distance in the function "upper block.dist" (059) when installing the
device in a high nozzle: upper blocking distance (UB) = nozzle height (H) + 50 mm.
L00-FMP4xxxx-14-00-06-xx-001
UB
H
50