Levelflex M FMP40 and FMP45 Installation
21
3.4.3 Installation for difficult to access process connections
Installation with remote electronic
• Follow installation instructions on Page 19 ff.
• Mount the housing on the wall or pipe (in vertical or horizontal position as required) as shown in
the diagram.
L00-FMP4xxxx-17-00-00-en-015
!
Note!
The connection tube cannot be disassembled at these points (1).
With remote electronics, for FMP40 temperatures up to 150 °C (302 °F) and for FMP45
temperatures up to 280 °C (536 °F) or 400 °C (752 °F) are permitted at the process connection
depending on the instrument version.
The ambient temperature for the connecting line (2) between the probe and electronics can be max.
105 °C.
The version with remote electronics consists of the probe, a connecting tube and the housing. If
they are ordered as a set, they are assembled on delivery.