21
3.4.3 Installation for difficult to access process connections
Installation with remote electronic
Follow installation instructions on Page 19 ff.
Mount the housing on the wall or pipe (in vertical or horizontal position as required) as shown in
the diagram.
L00-FMP4xxxx-17-00-00-en-015
!
Note!
The connection tube cannot be disassembled at these points (1).
With remote electronics, for FMP40 temperatures up to 150 °C (302 °F) and for FMP45
temperatures up to 280 °C (536 °F) or 400 °C (752 °F) are permitted at the process connection
depending on the instrument version.
The ambient temperature for the connecting line (2) between the probe and electronics can be max.
105 °C.
The version with remote electronics consists of the probe, a connecting tube and the housing. If
they are ordered as a set, they are assembled on delivery.
150
ENDRESS+HAUSER
Levelflex M
65 78
Ø 129
85
150
ENDRESS+HAUSER
Levelflex M
65 78
Ø 129
85
52
52
150
max. 80
min. 30
96
94
94
88
88
123
2765
112
190
75
Ø 76
1
1
4 x Ø 8,5
1
2
pipe
wall
Note min.
bend radius!