Installation Levelflex M FMP40 and FMP45
22
3.5 Turn housing
After mounting, the housing can be turned 350° in order to simplify access to the display and the
terminal compartment. Proceed as follows to turn the housing to the required position:
•Undo the fixing screws (1)
Turn the housing (2) in the required direction
Tighten up the fixing screws (1).
L00-FMP41Cxx-17-00-00-de-002
3.6 Post-installation check
After the measuring instrument has been installed, perform the following checks:
Is the measuring instrument damaged (visual check)?
Does the measuring instrument correspond to the measuring point specifications such as process
temperature/pressure, ambient temperature, measuring range, etc.?
Are the measuring point number and labeling correct (visual check)?
Is the measuring instrument adequately protected against rain and direct sunlight (see
Page 56 ff.)?
90°90°
90°90°
90°90°
1
1
2
2
F12/F23 housing T12 housing
allen key
4 mm/0.1