Commissioning Levelflex M FMP40 and FMP45
36
Basic Setup step 3/4:
Enter the length calibration:
Function "probe length"
l00-fmp4xxxx-20-00-00-de-004
Function "probe length"
By this function it is defined if the probe length has been changed after factory calibration. Any
adjustment is necessary only if the probe length has been changed!
Selection:
Not changed
Changed
L00-FMP4xxxx-19-00-00-de-009
In case the function "probe length " "changed" has been selected, in the following steps the new,
actual probe length can be entered.