Levelflex M FMP40 and FMP45 Commissioning
35
Function "Dielectric. const."
By this function the medium property of the upper product layer is defined. The dielectric value can
be defined also by clicking the tank smbol and by this opening the table book of dielectric values.
By entering the dielectic value, the threshold (noise level elimination) of the device is configured. If
it is necessary to adjust this threshold manually, this can be done in step 4.
l00-L00-FMP4xxxx-19-00-00-de-008
!
Note!
The table value of the dielectic constant may be different from the real product dielectric value.
Function "Dist. total level"
By this function, the distance to the overall level is defined. It is used to compensate the gas layer
above the product.
!
Note!
After entering the function “Dist. total level”, the parameter “upper blocking dist.” is adjusted to
the same value!