EasyManua.ls Logo

Endress+Hauser Liquiphant M FTL50H - Signal on Alarm; Connectable Load

Endress+Hauser Liquiphant M FTL50H
52 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Liquiphant M FTL50(H), FTL51(H)
10 Endress+Hauser
With M12x1 connector 52010285 / 52024216 (without LEDs)
With M12x1 connector 52018763 (with LEDs)
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 100 μA
Connectable load Load switched via the transistor and separate PNP connection, max. 55 V DC
Load current max. 350 mA (pulsed overload and short-circuit protection)
Residual current < 100 μA (with transistor blocked)
Capacitive load max. 0.5 μF at 55 V, max. 1.0 μF at 24 V
Residual voltage < 3 V (with transistor switched through)
L00-FTL5xxxx-16-05-
xx-xx-002
I
L
< 100 μA
L00-FTL2xxxx-07-05-
xx-xx-000
Safety mode Level Output signal LEDs
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
L00-FTL5xxxx-04-05-xx-xx-010
L00-FTL5xxxx-16-05-
xx-xx-001
I
L
< 100 μA
L00-FTL2xxxx-07-05-
xx-xx-000
Safety mode Level Output signal LEDs
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
L00-FTL5xxxx-04-05-xx-xx-011
rd
ye
gn
Max.
Min.
L+
12
I
L
I
L
< 100 µA
< 100 µA
L+
12
L+
14
L+
14
ye 1
ye 2
gn
Max.
Min.
L+
12
I
L
I
L
< 100 µA
< 100 µA
L+
12
L+
14
L+
14

Table of Contents

Other manuals for Endress+Hauser Liquiphant M FTL50H

Related product manuals