Liquiphant M FTL50(H), FTL51(H)
Endress+Hauser 7
Electronics FEL51 (AC, in compact housing)
Power supply Supply voltage: 19...253 V AC
Power consumption: < 0.83 W
Residual current consumption: < 3.8 mA
Short-circuit protection
FEM51 overvoltage protection: overvoltage category III
Electrical connection Two-wire AC connection
Output signal
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load For relays with a minimum holding power/rated power > 2.5 VA at 253 V AC (10 mA) or
> 0.5 VA at 24 V AC (20 mA)
Relays with a lower holding power/rated power can be operated by means of an RC module connected
inparallel
For relays with a maximum holding power/rated power < 89 VA at 253 V AC or < 8.4 VA at 24 V AC
Voltage drop across FEL51 max. 12 V
Residual current with blocked thyristor max. 3.8 mA
Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms) max. 1.5 A, max. 375 VA at 253 V or max. 36 VA at 24 V (not short-circuit proof)
Always connect in series with a load!
Check the following:
The residual current in
blocked state (up to 3.8 mA)
that for low voltage
the voltage drop across
the load is such that the
minimum terminal voltage
at the electronic insert
(19 V) when blocked is not
undershot.
the voltage drop across
the electronics when switched
through is
observed (up to 12 V).
That a relay
cannot de-energise with
holding power below 3.8 mA.
If this is the case, a resistor
should be connected parallel
to the relay.
(RC module available on request).
L00-FTL5xxxx-04-05-xx-en-008
MAX MIN
(Ground)
1
(BU)
3
(BN)
R
1.0 A
L1
N
PE
>19V
(Ground)
1
(BU)
2
(BK)
R
1.0 A
L1
N
PE
>19V
(GN/YE) (GN/YE)
1
3
1
2
FTL5#(H)- #######D3#
(Pg11)
FTL5#(H)- #######E3#
(NPT ½")
FTL5#(H)- #######C3#
(Ground)
R
1.0 A
L1
N
PE
>19V
(Ground)
R
1.0 A
L1
N
PE
>19V
Connector
or
Safety mode Level Output signal LEDs
green red
I
L
< 3.8 mA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
L00-FTL5xxxx-04-05-xx-xx-001a
Max.
Min.
13
12
12
I
L
I
L
< 3.8 mA
< 3.8 mA