Liquiphant M FTL50(H), FTL51(H)
6 Endress+Hauser
Electronic insert FEL51 (AC 2-wire)
Power supply Supply voltage: 19...253 V AC
Power consumption: < 0.83 W
Residual current consumption: < 3.8 mA
Short-circuit protection
FEM51 overvoltage protection: overvoltage category III
Electrical connection Two-wire AC connection
Output signal
Signal on alarm Output signal on power failure or in the event of damaged sensor: < 3.8 mA
Connectable load For relays with a minimum holding power/rated power > 2.5 VA at 253 V AC (10 mA) or
> 0.5 VA at 24 V AC (20 mA)
Relays with a lower holding power/rated power can be operated by means of an RC module connected
inparallel
For relays with a maximum holding power/rated power < 89 VA at 253 V AC or < 8.4 VA at 24 V AC
Voltage drop across FEL51 max. 12 V
Residual current with blocked thyristor max. 3.8 mA
Load switched directly into the power supply circuit via the thyristor.
Transient (40 ms) max. 1.5 A, max. 375 VA at 253 V or max. 36 VA at 24 V (not short-circuit proof)
Always connect in series with a load!
Check the following:
The residual current in blocked state
(up to 3.8 mA)
that for low voltage
the voltage drop across the load is such
that the minimum terminal voltage at the
electronic insert (19 V) when blocked is
not undershot.
the voltage drop across the electronics when
switched through is observed
(up to 12 V)
that a relay cannot de-energise with holding
power below 3.8 mA.
If this is the case, a resistor should be
connected parallel to the relay.
(RC module available on request).
When selecting the relay, pay attention to
the holding power/rated power
(See "Connectable load")
L00-FTL5xxxx-04-05-xx-en-007
L1
U~ max. 253 V AC
50/60 Hz
NNPE
(Ground)
1A
min.
19 V
12
FEL51
*
R
*
External load R
be connectedmust
Safety mode Level Output signal LEDs
green red
I
L
< 3.8 mA
L00-FTL2xxxx-07-05-
xx-xx-000
= load current
(switched through)
= residual current
(blocked)
= lit
= unlit
L00-FTL5xxxx-04-05-xx-xx-001
Max.
Min.
12
12
12
12
I
L
I
L
< 3.8 mA
< 3.8 mA