Micropilot FMR62 Commissioning (installation and configuration)
Endress+Hauser 17
The following parameters affect the safety function and are automatically adapted by the
device when configuring higher-ranking parameters (known as application parameters). It
is not possible to specify values because the higher-ranking parameters may be user-
configurable. This indirect setting is permitted in increased safety mode. However, it is not
permitted to change the parameters directly. If these parameters were changed directly,
only expert mode is available for selection during SIL/WHG confirmation.
Setup
Advanced setup → Level → Medium property
Advanced setup → Level → Max. draining speed liquid
Advanced setup → Level → Max. filling speed liquid
Advanced setup → Level → Blocking distance
Expert
Sensor → Distance → Dead time
Sensor → Distance → Integration time
Sensor → Distance → Max. integration time
Sensor → Distance → Delta at integration time
Sensor → Safety settings → Echo lost window right
Sensor → Safety settings → Echo lost window left
Sensor → Safety settings → Draining speed
Sensor → Safety settings → Filling speed
Sensor → Envelope curve → Envelope statistics down
Sensor → Envelope curve → Envelope statistics up
Sensor → Envelope curve → FAC offset
Sensor → Mapping → Map gap
Sensor → Mapping → End of mapping
Sensor → Echo fine adjustment → Fine adjustment mode
Sensor → Tank bottom evaluation → Min. amplitude TBD
Sensor → Tank bottom evaluation → Lower level area
Sensor → Echo tracking → Window size tracking
Sensor → Echo tracking → Maximal track counter
The following parameters affect the safety function and cannot be freely configured in
either the increased safety mode or in the expert mode. Instead they are automatically
changed by the device to the safety-oriented values mentioned at the start of SIL/WHG
confirmation.
"Setup" menu
Advanced setup → Safety settings → Output echo lost
Default value: Alarm
Advanced setup → Display → Backlight
Default value: Disable
"Diagnostics" menu
Simulation → Assign measurement variable
Default value: Off
Simulation → Current output simulation 1 to 2
Default value: Off
Simulation → Device alarm simulation
Default value: Off
Simulation → Diagnostic event simulation
Default value: Off
"Expert" menu
Sensor → Distance → Velocity filter
Default value: Off
Output → Current output 1 → Trim
Default value: Off
Output → Current output 2 → Trim
Default value: Off
Diagnostics → Simulation → Simulation distance on
Default value: Off