Micropilot FMR62 Repair and error handling
Endress+Hauser 27
• Spare parts kit FHX50
Visual inspection to check whether all parts are present and properly mounted
• Main electronics
• Visual inspection to check whether all parts are present and properly mounted
• Interference echo mapping must be recorded again
• Proof test, test sequence A or B
• I/O modules
• Visual inspection to check whether all parts are present and properly mounted
• Check the measurement at an arbitrary level
• Overvoltage protection OVP10/20
• Visual inspection to check whether all parts are present and properly mounted
• Check the measurement at an arbitrary level
• Terminals for I/O modules
• Visual inspection to check whether all parts are present and properly mounted
• Check the measurement at an arbitrary level
• Housing cover
Visual inspection to check whether all parts are present and properly mounted
• Seal of housing covers
Visual inspection to check whether all parts are present and properly mounted
• Housing filter (vent plugs)
Visual inspection to check whether all parts are present and properly mounted
• Securing clamps, housing
Visual inspection to check whether all parts are present and properly mounted
• Weather protection cover
Visual inspection to check whether all parts are present and properly mounted
• Mounting bracket
Visual inspection to check whether all parts are present and properly mounted
• Slip-on flange
• Visual inspection to check whether all parts are present and properly mounted
• Proof test, test sequence A or B
• Transmitter electronics of the remote display FHX50
Visual inspection to check whether all parts are present and properly mounted
• Cable of the remote display FHX50
Visual inspection to check whether all parts are present and properly mounted
Installation Instructions are supplied with the original spare part and can also be
accessed in the Download Area at www.endress.com
Send in replaced components to Endress+Hauser for fault analysis.
When returning the defective component, always enclose the "Declaration of
Hazardous Material and Decontamination" with the note "Used as SIL device in a
safety instrumented system.
Information on returns: http://www.endress.com/support/return-material
7.3 Modification
• Modifications to SIL devices by the user are not permitted as they can impair the
functional safety of the device
• Modifications to SIL devices on site at the user's plant are possible following approval by
the Endress+Hauser manufacturing center
• Modifications to SIL devices must be performed by staff who have been authorized to
perform this work by Endress+Hauser
• Only original spare parts from Endress+Hauser must be used for modifications
• All modifications must be documented in the Endress+Hauser W@M Device Viewer
• All modifications require a modification nameplate or the replacement of the original
nameplate.