Micropilot FMR62 Repair and error handling
Endress+Hauser 27
Spare parts kit FHX50
Visual inspection to check whether all parts are present and properly mounted
Main electronics
Visual inspection to check whether all parts are present and properly mounted
Interference echo mapping must be recorded again
Proof test, test sequence A or B
I/O modules
Visual inspection to check whether all parts are present and properly mounted
Check the measurement at an arbitrary level
Overvoltage protection OVP10/20
Visual inspection to check whether all parts are present and properly mounted
Check the measurement at an arbitrary level
Terminals for I/O modules
Visual inspection to check whether all parts are present and properly mounted
Check the measurement at an arbitrary level
Housing cover
Visual inspection to check whether all parts are present and properly mounted
Seal of housing covers
Visual inspection to check whether all parts are present and properly mounted
Housing filter (vent plugs)
Visual inspection to check whether all parts are present and properly mounted
Securing clamps, housing
Visual inspection to check whether all parts are present and properly mounted
Weather protection cover
Visual inspection to check whether all parts are present and properly mounted
Mounting bracket
Visual inspection to check whether all parts are present and properly mounted
Slip-on flange
Visual inspection to check whether all parts are present and properly mounted
Proof test, test sequence A or B
Transmitter electronics of the remote display FHX50
Visual inspection to check whether all parts are present and properly mounted
Cable of the remote display FHX50
Visual inspection to check whether all parts are present and properly mounted
Installation Instructions are supplied with the original spare part and can also be
accessed in the Download Area at www.endress.com
Send in replaced components to Endress+Hauser for fault analysis.
When returning the defective component, always enclose the "Declaration of
Hazardous Material and Decontamination" with the note "Used as SIL device in a
safety instrumented system.
Information on returns: http://www.endress.com/support/return-material
7.3 Modification
Modifications to SIL devices by the user are not permitted as they can impair the
functional safety of the device
Modifications to SIL devices on site at the user's plant are possible following approval by
the Endress+Hauser manufacturing center
Modifications to SIL devices must be performed by staff who have been authorized to
perform this work by Endress+Hauser
Only original spare parts from Endress+Hauser must be used for modifications
All modifications must be documented in the Endress+Hauser W@M Device Viewer
All modifications require a modification nameplate or the replacement of the original
nameplate.