Commissioning (installation and configuration) Micropilot FMR62
16 Endress+Hauser
4.6 Parameters and default settings for SIL mode
The following parameters affect the safety function. However, they may be freely
configured in accordance with the application. In increased safety mode, it is necessary to
confirm the configured values during the remainder of the commissioning process.
Confirmation is not required in expert mode. It is recommended to note down the
configured values!
Setup
• Empty calibration
• Full calibration
• Tank type
Only for liquids
• Bin type
Only for bulk solids
• Max. filling speed solid
Only for bulk solids
• Max. draining speed solid
Only for bulk solids
• Medium group
• Advanced setup → Level → Tank/silo height
The following parameters affect the safety function and are not freely configurable in
increased safety mode. Instead, they are automatically set by the device to the safety-
oriented values mentioned at the start of SIL/WHG confirmation. If these parameters are
to be set to other values, expert mode must be selected.
Setup
• Advanced setup → Level → Level correction
Default value: 0
• Advanced setup → Linearization → Linearization type
Default value: None
• Advanced setup → Current output 1 → Damping output
Default value: 0
Expert
• Sensor → Level → Distance offset
Default value: 0
• Sensor → Level → L max. drain speed
Default value: 0
• Sensor → Level → L max. fill speed
Default value: 0
• Sensor → Level → Level limit mode
Default value: Off
• Sensor → Level → Output mode
Default value: Level linearized
• Sensor → Safety settings → Jump delay echo lost
Default value: Off
• Sensor → Safety settings → Delay time echo lost
Default value: 3 s
• Sensor → Safety settings → Output echo lost
Default value: Alarm
• Sensor → Safety settings → In safety distance
Default value: Alarm
• Sensor → Echo tracking → Evaluation mode
Default value: No history
• Output → Current output 1 → Turn down
Default value: Off
• Output → Current output 1 → Measuring mode
Default value: Standard
• Communication → Configuration → HART address
Default value: 0