Flowmeter Proline 200 PROFINET with Ethernet-APL Electrical connection
Endress+Hauser 13
5 Electrical connection
5.1 Electrical safety
In accordance with applicable national regulations.
5.2 Connecting requirements
5.2.1 Required tools
For cable entries: Use corresponding tools
For securing clamp: Allen key 3 mm
Wire stripper
When using stranded cables: Crimper for wire end ferrule
For removing cables from terminal: Flat blade screwdriver ≤ 3 mm (0.12 in)
5.2.2 Requirements for connecting cable
The connecting cables provided by the customer must fulfill the following requirements.
Permitted temperature range
The installation guidelines that apply in the country of installation must be observed.
The cables must be suitable for the minimum and maximum temperatures to be expected.
Signal cable
PROFINET with Ethernet-APL
The reference cable type for APL segments is fieldbus cable type A, MAU type 1 and 3
(specified in IEC 61158-2). This cable meets the requirements for intrinsically safe
applications according to IEC TS 60079-47 and can also be used in non-intrinsically safe
applications.
Further details are provided in the Ethernet-APL Engineering Guideline
(https://www.ethernet-apl.org).
Cable diameter
Cable glands supplied:
M20 × 1.5 with cable  6 to 12 mm (0.24 to 0.47 in)
Plug-in spring terminals for device version without integrated overvoltage protection: wire
cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
Screw terminals for device version with integrated overvoltage protection: wire cross-
sections 0.2 to 2.5 mm
2
(24 to 14 AWG)