EasyManua.ls Logo

Endress+Hauser Proline 200 - 5.2.3 Connecting cable for remote version; 5.2.4 Fieldbus cable specification

Endress+Hauser Proline 200
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Electrical connection Flowmeter Proline 200 PROFINET with Ethernet-APL
14 Endress+Hauser
5.2.3 Connecting cable for remote version
Connecting cable (standard)
Standard cable
2 × 2 × 0.5 mm
2
(22 AWG) PVC cable with common shield (2 pairs, pair-stranded)
1)
Flame resistance According to DIN EN 60332-1-2
Oil resistance According to DIN EN 60811-2-1
Shielding Galvanized copper-braid, opt. density approx. 85 %
Cable length 5 m (15 ft), 10 m (30 ft), 20 m (60 ft), 30 m (90 ft)
Continuous operating
temperature
When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable can
move freely: –25 to +105 °C (–13 to +221 °F)
1) UV radiation may cause damage to the outer jacket of the cable. Protect the cable from exposure to sun as much
as possible.
Connecting cable (armored)
Cable, armored
2 × 2 × 0.34 mm
2
(22 AWG) PVC cable with common shield (2 pairs, pair-stranded)
and additional steel-wire braided sheath
1)
Flame resistance According to DIN EN 60332-1-2
Oil resistance According to DIN EN 60811-2-1
Shielding Galvanized copper-braid, opt. density approx. 85%
Strain relief and
reinforcement
Steel-wire braid, galvanized
Cable length 10 m (30 ft), 20 m (60 ft), 30 m (90 ft)
Continuous operating
temperature
When mounted in a fixed position: –50 to +105 °C (–58 to +221 °F); when cable can
move freely: –25 to +105 °C (–13 to +221 °F)
1) UV radiation may cause damage to the outer jacket of the cable. Protect the cable from exposure to sun as much
as possible.
5.2.4 Fieldbus cable specification
Cable type
In accordance with IEC 61158-2 (MBP), cable type A is recommended. Cable type A has a
cable shielding that guarantees adequate protection from electromagnetic interference and
thus the most reliable data transfer.
The electrical data of the fieldbus cable have not been specified. but determine important
characteristics of the design of the fieldbus, such as distances bridged, number of users,
electromagnetic compatibility, etc.
Cable type A
Cable structure Twisted, shielded twin-core cable

Table of Contents

Other manuals for Endress+Hauser Proline 200

Related product manuals