Electrical connection Flowmeter Proline 200 PROFINET with Ethernet-APL
18 Endress+Hauser
Connecting cable for remote version
Transmitter and sensor connection housing
In the case of the remote version, the sensor and transmitter are mounted separately from on
another and connected by a connecting cable. Connection is performed via the sensor
connection housing and the transmitter housing.
How the connecting cable is connected in the transmitter housing depends on the
measuring device approval and the version of the connecting cable used.
In the following versions, only terminals can be used for connection in the transmitter
housing:
Order code for "Electrical connection", option B, C, D
Certain approvals: Ex nA, Ex ec, Ex tb and Division 1
Use of reinforced connecting cable
In the following versions, an M12 device connector is used for connection in the
transmitter housing:
All other approvals
Use of connecting cable (standard)
Terminals are always used to connect the connecting cable in the sensor connection
housing (tightening torques for screws for cable strain relief: 1.2 to 1.7 Nm).
Connection via terminals