Electrical connection Flowmeter Proline 200 PROFINET with Ethernet-APL
24 Endress+Hauser
Connection via terminals
10 (0.4)
mm (in)
20 mm3 mm
1.2. 3.
4.
5. 6.
A0048825
1. Loosen the securing clamp of the connection compartment cover.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry . To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable and cable ends. In the case of stranded cables, also fit ferrules.
5. Connect cable in accordance with terminal assignment .
6.
L
WARNING
Housing degree of protection may be voided due to insufficient sealing of the
housing.
Screw in the screw without using any lubricant. The threads on the cover are coated
with a dry lubricant.
Firmly tighten the cable glands.
7. Reassemble the transmitter in the reverse order.