Installation Proline Promag 50
26 Endress+Hauser
Promag P tightening torques for ANSI
450 PN 25 20 × M 33 385
500 PN 10 20 × M 24 265
500 PN 16 20 × M 30 448
500 PN 25 20 × M 33 533
600 PN 10 20 × M 27 345
600 * PN 16 20 × M 33 658
600 PN 25 20 × M 36 731
* Designed acc. to EN 1092-1 (not to DIN 2501)
Nominal diameter ANSI Threaded fasteners Max. tightening torque
Pressure rating
[lbs]
PTFE PFA
[mm] [inch] [Nm] [lbf · ft] [Nm] [lbf · ft]
15 ½" Class 150 4 × ½" 6 4
15 ½" Class 300 4 × ½" 6 4
25 1" Class 150 4 × ½" 11 8 10 7
25 1" Class 300 4 × 5/8" 14 10 12 9
40 1 ½" Class 150 4 × ½" 24 18 21 15
40 1 ½" Class 300 4 × ¾" 34 25 31 23
50 2" Class 150 4 × 5/8" 47 35 44 32
50 2" Class 300 8 × 5/8" 23 17 22 16
80 3" Class 150 4 × 5/8" 79 58 67 49
80 3" Class 300 8 × ¾" 47 35 42 31
100 4" Class 150 8 × 5/8" 56 41 50 37
100 4" Class 300 8 × ¾" 67 49 59 44
150 6" Class 150 8 × ¾" 106 78 86 63
150 6" Class 300 12 × ¾" 73 54 67 49
200 8" Class 150 8 × ¾" 143 105 109 80
250 10" Class 150 12 × 7/8" 135 100
300 12" Class 150 12 × 7/8" 178 131
350 14" Class 150 12 × 1" 260 192
400 16" Class 150 16 × 1" 246 181
450 18" Class 150 16 × 1 1/8" 371 274
500 20" Class 150 20 × 1 1/8" 341 252
600 24" Class 150 20 × 1 ¼" 477 352
Nominal diameter EN (DIN) Threaded
fasteners
Max. tightening torque [Nm]
[mm] Pressure rating [bar] PTFE PFA
Q-Pulse Id
Active 30/09/2014
Page 26 of 52
Vendor Manual - Electromagnetic Flowmeter - Endress and Hauser - Model Proline Promag 50 - Operating Instructions
Q-Pulse Id VM454
Active 30/09/2014
Page 26 of 52

Other manuals for Endress+Hauser Proline Promag 50