Proline Promag 53 FOUNDATION Fieldbus
Endress+Hauser 5
<
Transmitter Promag 53 (remote version)
The Promag 53***-******G***** transmitter has a T6 temperature class rating when
installed in the EEx d housing for operation at ambient temperatures up to T
a
= 60 °C.
The maximum ambient temperature range is –20...+60 °C (depending on the area of
application).
!
Note:
At the specified medium temperatures, the equipment is not subjected to temperatures
impermissible for the temperature class in question.
Gas explosion protection
Determine the temperature class dependent on the ambient temperature and the
medium temperature.
Dust explosion protection
Determine the maximum surface temperature dependent on the ambient temperature
and the medium temperature.
Example:
Promag 53 P (PTFE), compact version:
T
a
= 45°C, T
M
= 110°C → T4 with maximum surface temperature of 135 °C.
Approvals
No. / approval type Description
DMT 00 ATEX E 017 X
DMT 00 ATEX E 019 X
DMT 00 ATEX E 021 X
EC type testing certificate according to directive
94/9/EC (ATEX)
(See Page 6 for notes on special instructions)
for the electric flow measuring system
Promag 53 FOUNDATION Fieldbus
Identification: 0 II2GD EEx resp.
0 II2(1)GD EEx
Measuring system Promag 53 FOUNDATION Fieldbus (compact version)
Promag 53***-***********.
G = FOUNDATION Fieldbus, EEx i
K = FOUNDATION Fieldbus
Promag 53***-***********K 0 II2GD EEx de [ia] IIC/IIB T1-T6 IP 6X
Promag 53***-***********G 0 II2(1)GD EEx de [ia] IIC/IIB T1-T6 IP 6X
Transmitter Promag 53 FOUNDATION Fieldbus (remote version)
Promag 53***-***********.
G = FOUNDATION Fieldbus, EEx i
K = FOUNDATION Fieldbus
Promag 53 0 II2(1)GD EEx de [ia] IIC/IIB T6 IP 6X
Sensor Promag (remote version)
Promag 53 H DN 2...100: 0 II2GD EEx e [ia] IIC/IIB T1-T6 IP 6X
Promag 53 P DN 15...600: 0 II2GD EEx e [ia] IIC/IIB T1-T6 IP 6X
Promag 53 W DN 65...1200: 0 II2GD EEx e [ia] IIC/IIB T1-T6 IP 6X