Installation Proline Promag P 100
14 Endress+Hauser
6 Installation
6.1
Installation conditions
No special measures such as supports are necessary. External forces are absorbed by the
construction of the device.
6.1.1 Mounting position
Mounting location
h ≥ 2 × DN
A0017061
Installation in down pipes
Install a siphon or a vent valve downstream of the sensor in down pipes whose length h
≥
5 m (16.4 ft). This precaution is to avoid low pressure and the consequent risk of damage to
the measuring tube. This measure also prevents the system losing prime, which could cause
air pockets.
A0017064
4 Installation in a down pipe
1 Vent valve
2 Pipe siphon
h Length of down pipe