Operation options Proline Promag P 100
40 Endress+Hauser
8.3.3 Via Ethernet network
This communication interface is present in the following device version:
Order code for "Output", option N: EtherNet/IP
A0016961
1 Ethernet network
2 Automation system, e.g. "RSLogix" (Rockwell Automation)
3 Workstation for measuring device operation: with Add-on Profile Level 3 for "RSLogix 5000" (Rockwell
Automation) or with Electronic Data Sheet (EDS)
4 Computer with Web browser (e.g. Internet Explorer) for accessing the integrated device Web server or
with "FieldCare" operating tool with COM DTM "CDI Communication TCP/IP"
5 Ethernet switch
8.3.4 Establishing a connection
For device version with EtherNet/IP communication type
Via service interface (CDI-RJ45) and "FieldCare" operating tool
1. Start FieldCare and launch the project.
2. In the network: Add a device.
The Add device window opens.
3. Select the CDI Communication TCP/IP
option from the list and press OK to confirm.
4. Right-click CDI Communication TCP/IP and select the Add device option in the context
menu that opens.
5. Select the desired device from the list and press OK
to confirm.
The CDI Communication TCP/IP (Configuration) window opens.
6. Enter the device address in the IP address field and press Enter to confirm:
192.168.1.212 (factory setting); if the IP address is not known, set DIP switch No. 10 on