Proline Prosonic Flow B 200 HART Technical data
Endress+Hauser 133
Assignable measured
variables
Volume flow
Corrected volume flow
Corrected methane volume flow
Mass flow
Energy flow
Methane fraction
Calorific value
Wobbe index
Temperature
Switch output
Switching behavior Binary, conductive or non-conductive
Switching delay Adjustable: 0 to 100 s
Number of switching
cycles
Unlimited
Assignable functions Off
On
Diagnostic behavior
Limit value
Volume flow
Corrected volume flow
Corrected methane volume flow
Mass flow
Energy flow
Methane fraction
Calorific value
Wobbe index
Temperature
Totalizer 1 to 3
Flow direction monitoring
Status
Low flow cut off
Signal on alarm Depending on the interface, failure information is displayed as follows:
Current output
4-20 mA
Failure mode Selectable (as per NAMUR recommendation NE 43):
Minimum value: 3.6 mA
Maximum value: 22 mA
Defined value: 3.59 to 22.5 mA
Actual value
Last valid value
HART
Device diagnostics Device condition can be read out via HART Command 48
Pulse/frequency/switch output
Pulse output
Failure mode Choose from:
Actual value
No pulses