Technical data Proline Prosonic Flow B 200 HART
132 Endress+Hauser
Current input
The measured values are written from the automation system to the measuring device via
the current input → 131.
HART protocol
The measured values are written from the automation system to the measuring device via
the HART protocol. The pressure transmitter must support the following protocol-specific
functions:
• HART protocol
• Burst mode
16.4 Output
Output signal Current output
Current output 1 4-20 mA HART (passive)
Current output 2 4-20 mA (passive)
Resolution < 1 µA
Damping Adjustable: 0.0 to 999.9 s
Assignable measured
variables
• Volume flow
• Corrected volume flow
• Corrected methane volume flow
• Mass flow
• Energy flow
• Methane fraction
• Calorific value
• Wobbe index
• Temperature
Pulse/frequency/switch output
Function Can be set to pulse, frequency or switch output
Version Passive, open collector
Maximum input values • DC 35 V
• 50 mA
Voltage drop • For ≤ 2 mA: 2 V
• For 10 mA: 8 V
Residual current ≤ 0.05 mA
Pulse output
Pulse width Adjustable: 5 to 2 000 ms
Maximum pulse rate 100 Impulse/s
Pulse value Adjustable
Assignable measured
variables
• Volume flow
• Corrected volume flow
• Corrected methane volume flow
• Mass flow
• Energy flow
Frequency output
Output frequency Adjustable: 0 to 1 000 Hz
Damping Adjustable: 0 to 999 s
Pulse/pause ratio 1:1