Proline Prosonic Flow B 200 HART Technical data
Endress+Hauser 135
Order code for "Output"
Minimum
terminal voltage
Maximum
terminal voltage
Option A
1)
2)
: 4-20 mA HART For 4 mA: ≥ DC 16 V
For 20 mA: ≥ DC 12 V
DC 35 V
Option B : 4-20 mA HART, pulse/frequency/switch
output
For 4 mA: ≥ DC 16 V
For 20 mA: ≥ DC 12 V
DC 35 V
Option C : 4-20 mA HART + 4-20 mA analog For 4 mA: ≥ DC 16 V
For 20 mA: ≥ DC 12 V
DC 30 V
Option D: 4-20 mA HART, pulse/frequency/switch
output, 4-20 mA current input
3)
≥ DC 12 V
DC 35 V
1) External supply voltage of the power supply unit with load.
2) For device versions with SD03 local display: The terminal voltage must be increased by DC 2 V if
backlighting is used.
3) Voltage drop 2.2 to 3 V for 3.59 to 22 mA
Power consumption Transmitter
Order code for "Output" Maximum power consumption
Option A: 4-20 mA HART 770 mW
Option B: 4-20 mA HART, pulse/
frequency/switch output
Operation with output 1: 770 mW
Operation with output 1 and 2: 2 770 mW
Option C: 4-20 mA HART + 4-20 mA
analog
Operation with output 1: 660 mW
Operation with output 1 and 2: 1 320 mW
Option D: 4-20 mA HART, pulse/
frequency/switch output, 4-20 mA current
input
Operation with output 1: 770 mW
Operation with output 1 and 2: 2770 mW
Operation with output 1 and input: 840 mW
Operation with output 1, 2 and input: 2840 mW
Current consumption Current output
For every 4-20 mA or 4-20 mA HART current output: 3.6 to 22.5 mA
If the option Defined value is selected in the Failure mode parameter :
3.59 to 22.5 mA
Current input
3.59 to 22.5 mA
Internal current limiting: max. 26 mA
Power supply failure Totalizers stop at the last value measured.
Configuration is retained in the device memory (HistoROM).
Error messages (incl. total operated hours) are stored.
Electrical connection →  27
Terminals For device version without integrated overvoltage protection: plug-in spring terminals
for wire cross-sections 0.5 to 2.5 mm
2
(20 to 14 AWG)
For device version with integrated overvoltage protection: screw terminals for wire cross-
sections 0.2 to 2.5 mm
2
(24 to 14 AWG)