Commissioning Prosonic T
30 Endress+Hauser
solid dusty conveyor belt Test: no filter
Dusty bulk solids Bulk solids with rapid level change All the filters can be switched off for
purposes of service and diagnosis.
L00-FMU30xxx-14-00-00-xx-007
L00-FMU30xxx-14-00-00-xx-005
The filters are set to detect even
relatively weak signals.
The averaging filters are set to small
values.
-> Rapid reaction time
-> Possibly unstable measured value
All filters off