Commissioning Turbimax CUS71D
22 Endress+Hauser
Around the interface you can define a window
entering a distance above and below the interface. The
signal that is inside the window is given preferential
consideration.
You can enter a distance from 0.0 to 10.0 m.
A signal outside the window must persist in order to be
considered valid.
Gate response rate determines the response time
with respect to the dynamic movements of the
window. You can enter a value from 0 to 50.
Increase Gate response rate to cause the gate to open
faster.
Treshold is a signal filter for consideration.
Increase this parameter to allow calculation of strong
signals.
Lower this parameter to allow calculation of softer
signals.
You can enter a value from 0 to 100.
(default = 20)
Diagnostics settings allows to adjust the diagnostics
performance.