Modbus Integrator's Guide for the Cordex® CXC HP Controller | 3 - Using Modbus
Table 3-30 AMPS HP modular inverter system data points (continued)
Name Register Format
Phase 3 DC Input Power 04:Input Register 32-bit Floating Point
Phase 3 Current Number Of Re-
dundant Inverters
04:Input Register 32-bit Floating Point
Phase 3 Number of Inverters De-
tected
04:Input Register 32-bit Floating Point
Phase 3 Number Of Inverters Off 04:Input Register 32-bit Floating Point
Phase 3 Number Of Inverters
Failed
04:Input Register 32-bit Floating Point
AC Group 1 Input Voltage 04:Input Register 32-bit Floating Point
AC Group 1 Input Current 04:Input Register 32-bit Floating Point
AC Group 1 Input Frequency 04:Input Register 32-bit Floating Point
AC Group 1 AC Input Power (VA) 04:Input Register 32-bit Floating Point
AC Group 1 Number Of Inverters
On
04:Input Register 32-bit Floating Point
AC Group 1 AC Input Power (W) 04:Input Register 32-bit Floating Point
AC Group 1 Number of Inverters
Detected
04:Input Register 32-bit Floating Point
AC Group 1 Number Of Inverters
Off
04:Input Register 32-bit Floating Point
AC Group 1 Number Of Inverters
Failed
04:Input Register 32-bit Floating Point
AC Group 2 Input Voltage 04:Input Register 32-bit Floating Point
AC Group 2 Input Current 04:Input Register 32-bit Floating Point
AC Group 2 Input Frequency 04:Input Register 32-bit Floating Point
AC Group 2 AC Input Power (VA) 04:Input Register 32-bit Floating Point
AC Group 2 Number Of Inverters
On
04:Input Register 32-bit Floating Point
AC Group 2 AC Input Power (W) 04:Input Register 32-bit Floating Point
AC Group 2 Number of Inverters
Detected
04:Input Register 32-bit Floating Point
AC Group 2 Number Of Inverters
Off
04:Input Register 32-bit Floating Point
Page 38 0350114-J0 Rev N