Modbus Integrator's Guide for the Cordex® CXC HP Controller | 3 - Using Modbus
Table 3-21 Polarium Protocol Bridge data points (continued)
Name Register Format
Lowest Full-Charging Voltage 04:Input Register 32-bit Floating Point
Highest Charge Current Percent-
age
04:Input Register 32-bit Floating Point
Highest Temperature 04:Input Register 32-bit Floating Point
Lowest Temperature 04:Input Register 32-bit Floating Point
Bay ID 04:Input Register 32-bit Floating Point
Shelf ID 04:Input Register 32-bit Floating Point
Slot ID 04:Input Register 32-bit Floating Point
Table 3-22 DC system data points
Name Register Format
AC Input Voltage High 02:Input Status Boolean
AC Input Voltage Low 02:Input Status Boolean
Long Term AC Input Fail 02:Input Status Boolean
Output Voltage High 02:Input Status Boolean
Output Voltage Very High 02:Input Status Boolean
Output Voltage Low 02:Input Status Boolean
Output Voltage Very Low 02:Input Status Boolean
Invalid System Voltage Reading 02:Input Status Boolean
Battery On Discharge (Deprecated) 02:Input Status Boolean
Rectifier Fail 02:Input Status Boolean
Rectifier Fail Count Very High 02:Input Status Boolean
Rectifier Fail Count High 02:Input Status Boolean
Rectifier Minor 02:Input Status Boolean
Rectifier Communication Lost 02:Input Status Boolean
AC Input Fail 02:Input Status Boolean
Fan Fail 02:Input Status Boolean
Battery Test (Deprecated) 02:Input Status Boolean
0350114-J0 Rev N Page 27