EVCO S.p.A.
c-pro 3 nano CHIL | Application manual ver. 1.0 | Code 144CP3NCHE104
page 43 of 90
8 REGULATIONS
8.1 Machine State
There are various procedures for turning the machine on and off:
1) use the designated ON/OFF key (this function is enabled with the PH05 parameter).
Switch-on – Press the designated key for about 2 seconds: if all the other enabled functions are present, the machine turns
on. Switch-off – Press the designated key for about 2 seconds: the machine turns off.
2) use the ON/OFF command from the digital input (this function is enabled with the PH07 parameter).
Switch-on – Closes the ON/OFF remote contact; if all the other enabled functions are present, the machine turns on.
Switch-on – If the ON/OFF remote contact is open, the machine “turns off from the digital input” indicated by “OFF D”.
3) use the supervision protocol (this function is enabled with the PH09 parameter).
Switch-on – Using the protocol, activate the ON status: if all other functions enabled are present, the machine switches on.
Switch-off – If the protocol deactivates the ON status, the machine “switches off from supervision protocol”, which is
indicated by “OFF S”.
4) use a programme (this function is enabled with the PH16 parameter).
Switch-on – If the date and time of the RTC indicate an ON statues: if all the other functions enabled are present, the
machine switches on. Switch-off – If the date and time of the RTC indicate an OFF status, the machine switches off.
The OFF status from digital input, supervision protocol, and programme are only accessible if the machine has been enabled by
pressing the key.
The ON/OFF key of the machine is the ON/STANDBY key.