EVCO S.p.A. EVFTFT618 | Installer manual ver. 2.2 | Code 144FTFT618E224
Page 40 of 62
rC5 0 10 °C 1 cooling neutral area value for the baking delay phase
rC6 -99 99 °C 2 pre-cooling set-point
Par. Min. Max. Unit Default Heating regulator
rH0 1 15 °C 2 rH3, rH4, rH5 parameters differential
rH1 -99 rH2 °C 0
minimum set-point that can be set for the recovery,
proving, making delay and manual heating phases
rH2 rH2 99 °C 40
maximum set-point that can be set for the recovery,
proving, making delay and manual heating phases
rH3 0 10 °C 1
heating neutral area value for the block, storage and
manual cooling phases
rH4 0 10 °C 1
heating neutral area value for the recovery, proving and
manual heating phases
rH5 0 10 °C 1 heating neutral area value for the baking delay phase
rH6 1 600 sec 60
cycle time for switch-on of the heating elements in the
event of a heating request (see also rh7)
rH7 1 600 sec 45 heating elements switch-on time within the cycle time rH6
rr0 1 10 - - - - 4 number of regulation steps in the recovery phase
rr1 1 rr2 % 25
increase percentage 1st recovery step (with respect to
100% total)
rr2 rr1 rr3 % 50
increase percentage 2nd recovery step (with respect to
100% total)
rr3 rr2 rr4 % 75
increase percentage 3rd recovery step (with respect to
100% total)
rr4 rr3 100 % 100
increase percentage 4th recovery step (with respect to
100%)
rr5 rr4 rr6 % - - - -
increase percentage 5th recovery step (with respect to
100%)
rr6 rr5 rr7 % - - - -
increase percentage 6th recovery step (with respect to
100%)
rr7 rr6 rr8 % - - - -
increase percentage 7th recovery step (with respect to
100%)
rr8 rr7 rr9 % - - - -
increase percentage 8th recovery step (with respect to
100%)
rr9 rr8 rr10 % - - - -
increase percentage 9th recovery step (with respect to
100%)
rr10 rr9 100 % - - - -
increase percentage 10th recovery step (with respect to
100%)
rL0 1 10 - - - - 4 number of resistor regulation steps in the proving phase
rL1 1 rL2 % 25
increase percentage 1st proving step (with respect to
100%)