34000 Autry Street, Livonia, MI 48150 • 800.968.5530 • Fax 734.419.0209 • www.hamiltonengineering.com • LIT91127 REV 3/09
GENERAL INFORMATION
B. EVO DIMENSIONS
Model
199
399
599
F
(
FPT
)
1.5"
2.0"
2.0"
1.0"
G
0.75"
0.75"
1.0"
0.75"
H
(
MPT
)
1.5"
1.5"
1.5"
1.0"
Width
16"
19"
19"
19"
Height
20.5"
33"
35"
33"
Depth
12"
19"
26.5"
19"
D
5"
3"
3"
4"
E
3"
3"
4"
5"
Right-hand view
SERVICE
RESET
LO
TEMPERATURE
CH
- +
Front-hand view
Condensate waste
Condensate trap cleaning point
Gas
(
G
)
Condensate trap cleaning point
Gas
(
G
)
Outlet
(
F
)
Relief Valve Location
Inlet
(
H
)
Air in Exhaust out
Outlet
(
F
)
Air in
(
D
)
Exhaust out
(
E
)
Inlet
(
H
)
Air Vent
Height
79-129 1.0" 0.75" 1.0"16" 20.5" 12" 3" 3"
299 1.5" 0.75" 1.5"19" 33" 19" 3" 3"
179-199.1
(FIGURE 1-1)
EVO DIMENSIONS
HW 79
HW 129
HW 179
HW 199.1
HW 199
HW 299
HW 399
HW 599
Model
80,000
136,300
186,000
199,999
199,999
300,000
399,999
630,000
Input
BTU/hr
77,600
132,890
181,002
193,999
193,999
291,000
387,999
611,100
Water Heater*
Output
BTU/hr
74,800
127,441
168,300
186,999
186,999
280,500
373,999
589,050
Boiler**
Output
BTU/hr
93
160
217
233
233
360
466
734
GPH*
Recovery
@10F T
116
199
272
291
291
450
582
917
GPH*
Recovery
@8F T
155
265
362
388
600
600
776
1223
GPH*
Recovery
@6F T
77 lbs.
77 lbs.
91 lbs.
91 lbs.
112 lbs.
111 lbs.
194 lbs.
234 lbs.
Shipping
Weight
(TABLE 1-1) EVO INFORMATION
*At 97% thermal efciency with 86
o
F incoming water to heat exchanger
**At 95% thermal efciency with 140
o
F incoming water to heat exchanger
Page 5 of 50