FX15 Controller Technical Bulletin
16
Address Selection
Through the dip-switches (see Figure 13), select the serial address of the
controller in the N2 Open network. The address selection is done in
binary mode.
Example.:• 1
st
ON, all others open
address = 2
0
+ 0
1
+ … = 1
• 1
st
ON, 4
th
ON, all others open
address = 2
0
+ 0
1
+ 0
2
+ 2
3
= 9
The address zero is not allowed. The factory default address
configuration is 1.
IMPORTANT: Cycle the controller power in order for new serial address to
become active.
Network Layout
Refer to the N2 Communication Bus Technical Bulletin (LIT-636018).