FX15 Controller Technical Bulletin
7
Detailed Procedures
Follow these instructions to properly install and connect the FX15.
!
WARNING: Risk of Electric Shock. Disconnect power supply before
making electrical connections. Contact with components carrying hazardous
voltage can cause electric shock and may result in injury or death.
Mounting Instructions
To mount an FX15:
1. Snap the controller onto the 35 mm (1.38 in.) rail for DIN rail
mounting. To release the controller, insert a screwdriver in Slots B
and lift the retaining clip. Since the retaining clip is spring-loaded,
you can also remove the controller without a screwdriver by
carefully pushing the controller up against the clip and then tilting
the top forward to release the top lug from the DIN rail.
2. Make wiring terminations with detachable connectors, which accept
1 x 1.5 mm
2
(0.002 in.
2
)/14 AWG cable. There are two types
available: screw and cage clamp connectors. For details, see
Ordering Codes.
Terminations of the Supervisor Link, Expansion Bus, and Remote
Display are made via the connectors provided with the controller.
3. Verify that the wiring has been correctly installed and that voltage
levels are appropriate for the various input signals according to the
application.
4. Set the jumpers and address switches of the controller as required.
For more information, see Jumper Details.