FX15 Controller Technical Bulletin
31
A99
NTC 2k2 ohm
Ni1000 JC
Ni1000 JC Extended
Ni1000 Landis and Gyr
Ni1000 DIN
Pt1000
Ratiometric
The measurement unit is also configurable to enable the controller to
propagate via network the measured value according to the appropriate
scale unit. Available configurable units are:
Temperature
Percentage
Air Pressure
Liquid Pressure
Flow
Concentration
Ampere
Voltage
A configurable filter constant in seconds is performed by the FX15 on
its Analog Inputs for the reduction of signal instability. An additional
Anti-Spike filter can be configured to limit the rate of change of the
input values to the value indicated by this attribute.
The FX15 provides a jumper configurable (Terminal 13) +5V AVPS
(Analog Voltage Power Supply) or a +16V External VDC, supply for
active analog input sensors (See
Jumper Details at page 12)
The EXT VDC can supply up to 80 mA for a maximum of four 0/4-20
mA active sensors. The AVPS can supply up to 10 mA for ratiometric
sensors.
Connecting Active 0-10 V Sensors
The FX15 can accept all the active temperature, pressure, flow and
humidity sensors providing 0-10 VDC signals.
Figure 32 shows the connection between an FX15 and an HT-9001
probe.