MPC-6000 / MPC-7000 / RND-2 INSTALLATION, OPERATION AND MAINTENANCE MANUAL
28
MPC-6000 / MPC-7000 / RND-2 OPERATING INSTRUCTIONS
Alarm Operation
In case of alarm, the Alarm LED flashes, LCD displays alarm conditions and the panel buzzer sounds steady. Local
audible and visual signals and remote alarm signals operate.
When an alarm occurs, proceed according to the established emergency plan. Assure that all personnel are
accounted for, and notify the Fire Department to advise of the alarm and/or verify that an automatic signal has been
received at the Fire Department.
Authorized Personnel Only
To acknowledge the alarm:
To acknowledge the alarm, press the Acknowledge button. The local buzzer will be silenced and the Alarm
LED will change from on-flashing to on-steady.
Note: On a networked system, the alarm may only be acknowledged at the node which initiates the
alarm or the RND-2.
To silence the alarm:
To silence the notification appliances after evacuation, where permitted, press the Alarm Silence button. The
silenceable notification appliances will be silenced. The Alarm Silenced LED will be lit.
Note: Do not reset the panel until the alarm has been cleared.
Warning: Alarm silence inhibit (if set) prevents the alarm from being silenced for a predetermined
time.
To reset panel after alarm:
When the alarm condition is corrected, return the panel to normal standby operation by pressing the System
Reset button.
Note: If the fan restart feature is implemented, the Independent or Global Fan Restart procedure must be
initiated to deactivate the hold-thru reset o utput type (and activate the fans).
Trouble Operation
Trouble is indicated by:
Trouble LED flashes, LCD displays trouble conditions. Panel buzzer sounds (pulsing).
To acknowledge the trouble:
Press the Acknowledge button. The Trouble LED turns on-steady and the buzzer turns off. When the trouble
condition has been cleared, you may need to reset the panel to restore to a normal standby condition.
Warning: Leaving the panel in a trouble condition may prevent a fire alarm condition from initiating a
fire alarm sequence.
Event Scrolling
Viewing Events on the System:
Events are displayed in the system by event priority (Alarm, Supervisory, Trouble) followed by event
occurrence (oldest to latest event) in a circular list.
If there are multiple events on the system, pressing the upper right button adjacent to the LCD displays the
next event that occurred (to latest event of highest priority). Pressing the lower right button adjacent to the
LCD displays the previous event that occurred (to the oldest event with the lowest priority).
Normal Standby Condition
The green AC Power On LED will be lit and no other indicators on.
For service, contact: ___________________________________________
Telephone Number: ___________________________________________
Frame these instructions and mount them near the control unit for operator reference.