DIVA D C24
46 EN
cod. 3542B920 - Rev 00 - 11/2022
Notes:
1. Parameters with more than one description vary their function and/or range in relation to the setting of the parameter
given in brackets.
2. Parameters with more than one description are reset to the default value if the parameter given in brackets is mo-
dified.
3. The Maximum Heating Power parameter can also be modified in Test Mode.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service
Menu, or exiting occurs automatically after 15 minutes.
“In” - Information Menu
Information PAR_INFO is available.
Press the Heating buttons to scroll the list of information in increasing or decreasing order. Press the DHW buttons to
display the value.
Table 4
Notes:
1. In case of damaged sensor, the card displays hyphens.
Press the Reset button to return to the Service Menu. Press the Reset button for 20 seconds to exit the card Service
Menu or exiting occurs automatically after 15 minutes.
P19
Solar deactivation temperature (b02=1) 0÷20°C
10
Solar deactivation temperature (b02=2) 0÷20°C
No effect on adjustment (b02=3) --
No effect on adjustment (b02=4) --
P20
Solar activation temperature (b02=1) 0÷20°C
10
Solar ignition temperature (b02=2) 0÷20°C
No effect on adjustment (b02=3) --
No effect on adjustment (b02=4) --
P21
Solar standby time (b02=1) 0-20 seconds
10
Solar standby time (b02=2) 0-20 seconds
No effect on adjustment (b02=3) --
No effect on adjustment (b02=4) --
Index Description Range
t01 NTC Heating sensor (°C) between 05 and 125°C
t02 NTC Safety sensor (°C) between 05 and 125°C
t03 NTC DHW sensor (°C) between 05 and 125°C
t04 NTC External sensor (°C) between -30 and 70°C (negative values flash)Without NTC = --
L05 Actual burner power (%) 00%=Min., 100%=Max.
F06 Actual Flame resistance (kOhm) 00-99 kOhm (-- = burner off)
St07 NOT AVAILABLE FOR THIS MODEL /
F08 Actual DHW draw-off (L min/10) L min/10 over 99 flashing 3 figures
PP09 Actual modulating pump speed (%) 00-100% not working in this model
Index Description Range to use DIVA D C24

Table of Contents

Other manuals for Ferroli DIVA D C24

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ferroli DIVA D C24 and is the answer not in the manual?

Ferroli DIVA D C24 Specifications

General IconGeneral
BrandFerroli
ModelDIVA D C24
CategoryPortable Generator
LanguageEnglish