BOILER CONTROLLER - SERVICE MENU
Press the heating buttons (details 3 and 4 - fig. 151) to increase or decrease the power (Minimum=0%, Maximum=100%).
By pressing the DHW “-” button (detail 1 - fig. 151), boiler output is immediately adjusted to minimum (0%).
Wait about 1 minute for stabilisation.
By pressing the DHW “+” button (detail 2 - fig. 151), boiler output is immediately adjusted to maximum (100%).
If the TEST mode is activated and enough hot water is drawn to activate the DHW mode, the boiler remains in TEST mode but the 3-way valve goes to DHW.
To deactivate the TEST mode, press the heating buttons simultaneously (details 3 and 4 - fig. 151) for 5 seconds.
The TEST mode is automatically disabled in any case after 15 minutes or on stopping of hot water drawing (if enough hot water is drawn to activate DHW mode).
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see “10.1 Adjustments” on page 67). Press the heating buttons detail 3 - fig. 151 to increase or decre-
ase the power (min. = 00 - max. = 100). Press the reset button within 5 seconds and the max. power will remain that just set. Exit TEST mode (see “10.1 Adjustments”
on page 67).
Service menu
ONLY QUALIFIED PERSONNEL CAN ACCESS THE SERVICE MENU AND MODIFY PARAMETERS..
The card Service Menu is accessed by pressing the Reset button for 10 seconds.
The display will show: “100” and the message “co” flashing.
Then set “103” with the DHW buttons, with the heating buttons set “123” and confirm by pressing the Reset button.
Five submenus are available: press the Heating buttons to select, in increasing or decreasing order, “tS”, “sC”, “In”, “Hi” or “rE”.
To enter the selected menu, press the reset button once.
“tS” - Transparent Parameters Menu
Press the Heating buttons to scroll the list of parameters in increasing or decreasing order. Press the DHW buttons to view or modify the value of a parameter: the
change will be automatically saved.
0=Disattivato Descrizione Range Default
b01 Boiler type selection 1 = BITHERMAL INSTANTANEOUS
2 = MONOTHERMAL HEATING only (also with OPTIONAL STORAGE
TANK)
3 = MONOTHERMAL COMBI
4 = MONOTHERMAL with STORAGE TANK
3=RRT
b02 Exchanger type 1 ÷ 4 1
b03 Absolute Maximum Heating Power (b02=1) 0 ÷ 100% (Do not modify the value) 83%
Absolute Maximum Heating Power (b02=2) 0 ÷ 100% (Do not modify the value) 85%
Absolute Maximum Heating Power (b02=3) 0 ÷ 100% (Do not modify the value) 85%
Absolute Maximum Heating Power (b02=4) 0 ÷ 100% (Do not modify the value) 90%
b04 System water pressure protection selection 0=Pressure switch, 1=Pressure transducer 0=Pressure switch
b05 Summer / Winter function 0 = WINTER - SUMMER - OFF
1 = WINTER - OFF
0 = Enabled
b06 Variable input contact operation selection (b01=1) 0=Flowmeter off, 1=System thermostat, 2=Second room thermostat,
3=Warning/Notification, 4=Safety thermostat
2=Second room therm.
Variable input contact operation selection (b01=2) 0=Continuous Comfort, 1=System thermostat, 2=Second room thermo-
stat, 3=Warning/Notification, 4=Safety thermostat
2=Second room therm.
Variable input contact operation selection (b01=3) 0=Flowmeter off, 1=System thermostat, 2=Second room thermostat,
3=Warning/Notification, 4=Safety thermostat
2=Second room therm.
Variable input contact operation selection (b01=4) 0=Continuous Comfort, 1=System thermostat, 2=Second room thermo-
stat, 3=Warning/Notification, 4=Safety thermostat
2=Second room therm.
b07 Relay card LC32 operation selection (b01=1) 0=External gas valve, 1=Alarm, 2=System loading solenoid valve, 3=so-
lar 3-way valve, 4=Second heating pump, 5=Alarm2, 6=Burner On,
7=Frost protection active.
0=External gas valve
Relay card LC32 operation selection (b01=2) 0=External gas valve, 1=Alarm, 2=System loading solenoid valve,
3=Legionella pump, 4=Second heating pump, 5=Alarm2, 6=Burner On,
7=Frost protection active.
0=External gas valve
Relay card LC32 operation selection (b01=3) 0=External gas valve, 1=Alarm, 2=System loading solenoid valve, 3=so-
lar 3-way valve, 4=Second heating pump, 5=Alarm2, 6=Burner On,
7=Frost protection active.
0=External gas valve
Relay card LC32 operation selection (b01=4) 0=External gas valve, 1=Alarm, 2=System loading solenoid valve, 3=so-
lar 3-way valve, 4=Second heating pump, 5=Alarm2, 6=Burner On,
7=Frost protection active.
0=External gas valve
b08 Hours without DHW drawn (b01=1) 0-24 hours (time for temporary deactivation of comfort mode without
drawing)
24 hours
No effect on adjustment (b01=2) 0-24 hours (time for temporary deactivation of comfort mode without
drawing)
24 hours
Hours without DHW drawn (b01=3) 0-24 hours (time for temporary deactivation of comfort mode without
drawing)
24 hours
No effect on adjustment (b01=4) 0-24 hours (time for temporary deactivation of comfort mode without
drawing)
24 hours
b09 Fault 20 status selection 0=Deactivated, 1=Enabled (Only for versions with pressure transducer) 0=Deactivated
b10 Comfort burner on time (b01=1) 0-40 seconds 15 seconds
Not implemented (b01=2) -- --
Not implemented (b01=3) -- --
Not implemented (b01=4) -- --
b11 Flowmeter timing (b01=1) 0=Deactivated, 1-10=seconds 0=Deactivated
Storage tank preparation mode (b01=2) 0=Fixed primary, 1=Linked to setpoint, 2=Ramp 0=Fixed primary
Flowmeter timing (b01=3) 0=Deactivated, 1-10=seconds 0=Deactivated
Storage tank preparation mode (b01=4) 0=Fixed primary, 1=Linked to setpoint, 2=Ramp 0=Fixed primary

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Ferroli OMNIA HYBRID C and is the answer not in the manual?

Ferroli OMNIA HYBRID C Specifications

General IconGeneral
BrandFerroli
ModelOMNIA HYBRID C
CategoryHeat Pump
LanguageEnglish

Related product manuals